809.5 Fire Alarms - Smoke/Carbon Monoxide Detector
809.5.1 Building Fire
Alarm System. Where a building fire alarm system is provided, the
system wiring shall be extended to a point within the residential
dwelling unit in the vicinity of the residential dwelling unit smoke
detection system.
809.5.1.1 Alarm Appliances. Where alarm
appliances are provided within a residential dwelling unit as part of
the building fire alarm system, they shall comply with 702.
809.5.1.2 Activation. All visible alarm
appliances provided within the residential dwelling unit for building
fire alarm notification shall be activated upon activation of the
building fire alarm in the portion of the building containing the
residential dwelling unit.
809.5.2 Residential Dwelling Unit Smoke Detection System. Residential dwelling unit smoke detection systems shall comply with NFPA 72 (1999 or 2002 edition) (incorporated by reference, see "Referenced Standards" in Chapter 1).
809.5.2.2 Activation. All visible alarm
appliances provided within the residential dwelling unit for smoke
detection notification shall be activated upon smoke detection.
809.5.3 Interconnection. The same visible
alarm appliances shall be permitted to provide notification of
residential dwelling unit smoke detection and building fire alarm
activation.
809.5.4 Prohibited Use. Visible alarm
appliances used to indicate residential dwelling unit smoke detection
or building fire alarm activation shall not be used for any other
purpose within the residential dwelling unit.
Copied with permission from:
ADA and ABA Accessibility Guidelines for Buildings and Facilities
Published in the Federal Register on July 23, 2004